Fixed Nozzle Desuperheater (FND)

Features
  • Single nozzle Kv as low as 0.0162 m3/hr and as high as 1.6 m3/hr
  • Number of nozzles limited only by pipeline diameter
  • For use on all pipe sizes 6" and above
  • Ideal for use in conjunction with water control valve and control system
  • Turndown ratio up to 4 : 1 (Depending on water quantity)


Notes

  • Minimum pipe size required for installation of FND is 150mm
  • Water pressure should be minimum 7 bar more than the steam pressure
  • maximum recommended pressure difference between steam and water is 45 bar. if it exceeds 45 bar then install pressure control valve in waterline to reduce water pressure within limits
  • Spray water should be very clean (equivalent to boiler feedwater)
  • IBR approval shall be provided for individual components
  • Turndown ratio up to 1 : 4


Typical Sizes

  • Steam side flange : 4" and water side flange 1" / 1 1/2" OR Steam side flange : 6" and water side flange 2"
  • Pressure rating :upto ANSI #2500


Advantages

  • Custom made for any size, standard or range
  • Simple installation
  • Can be used for higher pipe size and low steam pressure
  • No moving parts